Outside temperature sensor QAC3161 QAC3171
Active sensor for acquiring the outside temperature. For use in heating, ventilation and air conditioning plants.
The QAC31.. may be used as an high-quality room sensor.
Sensing element, temperature Pt1000
Measuring range, temperature -50...50 °C
Time constant 20 min
Connection, electrical Screw terminals
Degree of protection IP65
Dimensions (W x H x D) 80 x 88 x 39 mm
DC 0...10 V DC 13.5...35 AC 24 At -50...50 °C: ±0.9 BPZ:QAC3161 QAC3161
DC 4...20 mA DC 13.5...35 At -50...50 °C: ±0.9 BPZ:QAC3171 QAC3171