Installation guide of Room sensors
Installation guide of Room sensors
Install sensors at a height of 1.5 m in occupied spaces, and at least 50 cm from the adjacent wall.
Do not install where sensor will be exposed to direct solar radiation.
Always use a thermally-insulated backing when fitting to solid walls (steel, concrete etc.)
Do not install on external walls.
Avoid recesses (e.g. shelving) and alcoves.
Do not install near lamps or above radiators.
Avoid chimney walls.
Do not install directly adjacent to doors.
Do not install behind curtains.
Do not fit to walls concealing hot-water pipes.
Seal gaps between cable/plastic tubing and conduit. Otherwise measurements will be falsified by incorrect circulation of the air.