Installation guide of Probe Temperature sensors · Air
Installation guide of Probe Temperature sensors · Air
Allow a distance of at least 50 mm between the heat exchanger and the sensor.
The entire length of an averaging sensor must be installed fully inside the air duct.
The sensor element must be distributed evenly over the full cross-section.
If air washers are used for humidification, install the sensor element downstream of the eliminator plate, in the direction of air flow.
Do not bend the capillary too tightly (radius of bend must not be less than 50 mm).
When routing the capillary through internal or external walls, for example, always use a lined and insulated conduit.
Where the capillary passes through sheet metal,protect it with a rubber gromme (to prevent shearing).